Key Features
- SmartOnline high-performance UPS system is ideal for critical voice, data, medical and industrial network applications
- True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 100/110/120V (user selectable) under all usage conditions
- Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
- Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
- Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
- Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 100/110/120V (+/-2%) values
- Standard internal battery set offers 14 min. runtime at half load (600W) and 5 min. at full load (1200W)
- Extended runtime available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible) external battery packs
- Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
- Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 in.
- Ships with all mounting accessories for 4-post rackmount installation
- Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
- Optional 2-9USTAND accessory enables small-footprint upright tower placement
- Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
- Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
- HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
- Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP
- UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment and UPS line to battery power voltage setpoints
- Built-in Emergency Power Off (EPO) interface with cable
- NEMA 5-15P input plug; NEMA 5-15R output receptacles
- Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (bank one has 2 outlets, bank two has 4 outlets)
- Front panel LEDs offer current monitoring and battery charge level information
- UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required
- Single-line tel/DSL or network Ethernet surge suppression
- $250,000 Ultimate Lifetime Insurance
Package Includes
- SU1500RTXL2Ua UPS System
- PowerAlert Software CD
- 1 x 6-ft. USB Cable
- 1 x 6-ft. DB9 Cable
- 4-Post Rackmounting Hardware
- Owner's Manual
OUTPUT | |
Output Volt Amp Capacity (VA) | 1500 |
Output kVA capacity (kVA) | 1.5 |
Output Watt Capacity (watts) | 1200 |
Output kW capacity | 1.2 |
Output power factor | 0.8 |
Crest Factor | 3:01 |
Nominal Output Voltage(s) Supported | 100V; 110V; 120V |
Nominal Voltage details | 120V default |
Frequency compatibility | 50 / 60 Hz |
Frequency compatibility details | Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start |
Output voltage regulation (line mode) | +/- 2% |
Output voltage regulation (Economy line mode) | +/- 10% |
Output voltage regulation (Battery mode) | +/- 2% |
Built-in UPS output receptacles | 6 5-15R outlet(s) |
Built-in controllable switched load banks | Two switchable 5-15R load banks (bank 1 - two outlets, bank 2 - four outlets) |
Output AC waveform (AC mode) | Sine wave |
Output AC waveform (battery mode) | Pure Sine wave |
INPUT | |
Rated input current (at maximum load) | 12A |
Nominal Input Voltage(s) Supported | 100V AC; 110V AC; 120V AC |
UPS input connection type | 5-15P |
Input circuit breaker | 20A |
UPS Input cord length (ft.) | 10 |
UPS Input cord length (m) | 3 |
Recommended Electrical Service | 15A 120V |
Phase | Single-Phase |
BATTERY | |
Full load runtime (minutes) | 5 min. (1200w) |
Half load runtime (minutes) | 14 min. (600w) |
Expandable battery runtime | Extended runtime supported via optional external battery packs |
External battery pack compatibility | BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible) |
DC system voltage (VDC) | 48 |
Battery recharge rate (included batteries) | Less than 6 hours from 10% to 80% |
Replacement battery cartridge (internal UPS battery replacement) | RBC94-2U |
Battery Access | Front panel battery access door |
Battery replacement description | Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION | |
Voltage regulation description | Online, double-conversion power conditioning |
Overvoltage correction | 2% output voltage regulation during overvoltages to 150 |
Undervoltage correction | 2% output voltage regulation during undervoltages to 80 |
Severe undervoltage correction | 2% output voltage regulation during undervoltages to 65 (under 70% load only) |
LEDS ALARMS & SWITCHES | |
LED Indicators | 14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats |
Alarms | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
Alarm cancel operation | Power-fail alarm can be silenced using alarm-cancel switch |
Switches | 2 switches control off/on power status and alarm-cancel/self-test operation |
SURGE / NOISE SUPPRESSION | |
UPS AC suppression joule rating | 600 |
UPS AC suppression response time | Instantaneous |
UPS Dataline suppression | 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
EMI / RFI AC noise suppression | Yes |
PHYSICAL | |
Installation form factors supported with included accessories | 4 post 19 inch rackmount |
Installation form factors supported with optional accessories | 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND) |
Primary form factor | Rackmount |
UPS / Power Module dimensions in primary form factor (height x width x depth / inches) | 3.5 x 17.5 x 19 |
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) | 8.9 x 44.4 x 48.3 |
Rack Height | 2U |
Secondary form factor | Tower (requires 2-9USTAND) |
UPS / Power Module weight (lbs) | 44.1 |
UPS / Power Module weight (kg) | 2000% |
UPS Shipping dimensions (height x width x depth / inches) | 9.8 x 20.2 x 24 |
UPS Shipping dimensions (height x width x depth / cm) | 24.8 x 51.4 x 61 |
Shipping weight (lbs) | 54 |
Shipping weight (kg) | 2450% |
Cooling method | Fan |
UPS housing material | Steel |
ENVIRONMENTAL | |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity | 0 to 95%, non-condensing |
AC mode BTU / hr. (full load) | 60970% |
AC economy mode BTU / hr. (full load) | 260.4 |
Battery mode BTU / hr. (full load) | 664.2 |
AC mode efficiency rating (100% load) | 87% |
AC economy mode efficiency rating (100% load) | 94% |
COMMUNICATIONS | |
Communications interface | USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface |
Network monitoring port description | Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications |
PowerAlert software | Included |
Communications cable | USB and DB9 cabling included |
WatchDog compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
LINE / BATTERY TRANSFER | |
Transfer time | No transfer time (0 ms.) in online, double-conversion mode |
Low voltage transfer to battery power (setpoint) | 80V (100% load), 65V ( <70% load) |
High voltage transfer to battery power (setpoint) | 150 |
SPECIAL FEATURES | |
Cold Start (startup in battery mode during a power failure) | Cold-start operation supported |
High availability UPS features | Automatic inverter bypass; Hot swappable batteries |
Green & high efficiency features | High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation |
CERTIFICATIONS | |
UPS Certifications | Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI) |
WARRANTY | |
Product Warranty Period (Worldwide) | 2-year limited warranty |
Connected Equipment Insurance (U.S., Canada & Puerto Rico) | $250,000 Ultimate Lifetime Insurance |