6000VA UPS Smart Online High Efficiency 6U RM 6kVA 208-240V

This product is very heavy and normally ships on a pallet. Specific arrangements must be made with Hummingbird Networks to arrange delivery after order is submitted.

 

 

Key Features

  • Tripp Lite SU6000RT4UTF 6000VA / 6kVA / 5400 watt on-line, double-conversion UPS system in a 6U rack/tower compatible configuration (4U power module plus 2U low-voltage transformer; at 208V nominal, output is limited to 4992 watts)
  • Full-time active power conditioning maintains clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise
  • Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
  • Detachable back panel PDU contains input line cord connection, output receptacles and manual bypass switch to support hot-swappable whole UPS replacement with no interruption to connected equipment
  • L6-30P input plug
  • UPS supported outlets include two L6-30R, two L6-20R, 8 5-15/20R and 4 5-15R outlets
  • Included rail kit supports 4U 19 inch rackmount installation in 4 post racks
  • Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (2 required for SU6000RT4UTF)
  • Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UTF)
  • Maximum installed rack depth of only 21.8 in. / 55.3 cm
  • Maintains full-time sine wave output within 2% of selected 208/240V and 120V nominal at 60Hz in double conversion mode
  • Corrects brownouts to 156V at full load (100V at 50% load or less)
  • Corrects overvoltages to 290V at full load (300V at 90% load or less)
  • Double-conversion operation offers full-time AC to DC, then DC to AC conversion to maintain perfectly regulated sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
  • High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs
  • Network-grade AC surge and noise suppression
  • Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232, USB and optional SNMP card slot interfaces
  • UPS card slot supports one card-based network interface option (part # SNMPWEBCARD) or dry-contact monitoring accessory (part # RELAYIOCARD)
  • Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
  • Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
  • Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)
  • HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
  • Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250 SNMP-enabled UPS, PDU and other networking devices
  • Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS functions with support for a variety of control options to support advanced UPS settings and configurations
  • LED/LCD display panel rotates for viewing in rackmount or tower configurations
  • Supports Emergency Power Off (EPO) via built-in interface
  • Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement
  • BP192V12-3U external battery packs are field replaceable and hot swappable
  • Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
  • $250,000 connected equipment insurance;
OUTPUT  
Output Volt Amp Capacity (VA) 6000
Output kVA capacity (kVA) 6
Output Watt Capacity (watts) 5400
Output kW capacity 5.4
Output power factor 21:36
Output Capacity Details Output capacity de-rates to 4992 watts when used at 208V nominal
Crest Factor 3:01
Nominal Output Voltage(s) Supported 120V; 208V; 240V
Frequency compatibility 60 Hz
Frequency compatibility details Output frequency regulation +/-0.05Hz (free running)
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 2%
Built-in UPS output receptacles 4 5-15R outlet(s); 8 5-15/20R outlet(s);
2 L6-20R outlet(s); 2 L6-30R outlet(s)
Output receptacle details Output receptacles and input line cord are mounted on a
detachable PDU backplate with bypass switch to enable
hot-swappable power module replacement
Output circuit breaker High voltage 20A breaker protects L6-20R outlets,
L6-30R outlets are unbreakered; Low voltage 20A
breakers protect 4 5-15/20R outlets each; Low voltage
15A breakers protect 2 5-15/20R outlets each
Output AC waveform (AC mode) Pure Sine wave
Output AC waveform (battery mode) Pure Sine wave
INPUT  
Rated input current (at maximum load) 31.9A (200V), 30.6A (208V), 29A (220V),
27.7A (230V), 26.6A (240V)
Nominal Input Voltage(s) Supported 208V AC; 240V AC
Nominal input voltage description Factory configured to 208V
UPS input connection type L6-30P
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 30A
Phase Single-Phase
BATTERY  
Full load runtime (minutes) 2 min. (5400 watts)
Half load runtime (minutes) 8.5 min. (2700 watts)
Expandable battery runtime Runtime is expandable with external battery packs
External battery pack compatibility BP192V12-3U; BP192V557C-1PH; BP192V787C-1PH;
BP192V1037C-1PH; BP192V1407C-1PH
DC system voltage (VDC) 192
Battery recharge rate (included batteries) 6 hours from 10% to 90% (internal batteries)
Replacement battery cartridge
(internal UPS battery replacement)
RBC5-192
Battery Access Front panel battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION  
Voltage regulation description Online, double-conversion power conditioning
Overvoltage correction Corrects overvoltages as high as
300V (<90% load) and 280V (full load)
Undervoltage correction Corrects undervoltages as low as
100 (<50% load) and 155V (full load); derates linearly
LEDS ALARMS & SWITCHES  
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass
mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Alarms Unique audible alarms for all major UPS,
environmental and power conditions (see manual)
Alarm cancel operation Alarm cancel switch
Switches Includes main power off/on switch, plus 2 switches to set
and execute scrollable LCD functions. A manual bypass
switch featured on the detachable PDU allows for complete
removal of the UPS during routine maintenance without
disrupting power to connected loads.
SURGE / NOISE SUPPRESSION  
UPS AC suppression response time Instantaneous
EMI / RFI AC noise suppression Yes
PHYSICAL  
Installation form factors supported
with included accessories
4 post 19 inch rackmount
Included mounting accessory description Two sets of adjustable 4 post 19 inch
rackmount installation rails included
Installation form factors supported
with optional accessories
2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
Optional mounting accessory notes 2 post rackmount installation requires TWO 2POSTRMKITHD
accessories, Tower installation requires ONE 2-9USTAND accessory.
Primary form factor Rackmount
UPS / Power Module dimensions
in primary form factor
(height x width x depth / inches)
6.85 x 17.5 x 20.7
UPS / Power Module dimensions
in primary form factor
(height x width x depth / cm)
17.4 x 44.5 x 52.6
Installed whole system maximum
rack depth (inches)
2180%
Installed whole system maximum
rack depth (cm)
55.4
Rack Height 6U
Secondary form factor Tower
UPS / Power Module weight (lbs) 116.2
UPS / Power Module weight (kg) 5280%
Stepdown transformer dimensions
(height x width x depth / inches)
3.5 x 17.5 x 21.8
Stepdown transformer dimensions
(height x width x depth / cm)
8.8 x 44.5 x 55.4
Stepdown transformer weight (lbs) 7260%
Stepdown transformer weight (kg) 3300%
UPS Shipping dimensions
(height x width x depth / inches)
22.5 x 25 x 30
UPS Shipping dimensions
(height x width x depth / cm)
57.2 x 63.5 x 76.2
Shipping weight (lbs) 293
Shipping weight (kg) 13300%
Cooling method Fans
UPS housing material Steel
ENVIRONMENTAL  
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 176700%
AC economy mode BTU / hr. (full load) 70700%
Battery mode BTU / hr. (full load) 178400%
AC mode efficiency rating (100% load) 90%
AC economy mode efficiency rating (100% load) 96%
Operating Elevation (ft.) 0-3000m (0 to 10,000 ft.)
Audible Noise 60 dBA at front side 1 meter
Operating Elevation (m) 0-3000 m
COMMUNICATIONS  
Communications interface USB (HID enabled); DB9 Serial; EPO (emergency power off);
Slot for SNMP/Web interface
Network monitoring port description Additional contact closure support with optional
RELAYIOCARD and RELAYIOMINI interface cards.
RELAYIOMINI installation requires removal of panel
containing USB ports
PowerAlert software Included
Communications cable USB, DB9 serial and EPO cables included
WatchDog compatibility Yes
LINE / BATTERY TRANSFER  
Transfer time No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint) 156V (full load) / 100V (50% load or less, derates linearly)
High voltage transfer to battery power (setpoint) 280V (full load) / 300V (90% load or less)
SPECIAL FEATURES  
Cold Start (startup in battery
mode during a power failure)
Cold-start operation supported
High availability UPS features Automatic inverter bypass; Manual bypass switch;
Detachable hot-swap PDU; Hot swappable UPS
power module; Hot swappable batteries
Green & high efficiency features High efficiency economy mode operation; Support for daily
startup and shutoff; Schedulable daily hours of economy
mode operation
CERTIFICATIONS  
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada);
Meets FCC Part 15 Category A (EMI);
ROHS (Restriction of Hazardous Substances)
UPS Certification details IEC 61000-4-5 1995 B Surge Immunity
WARRANTY  
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime Insurance