3000VA UPS Smart Online Tower Extended Run PureSine 3kVA 120V 7 outlets

 

 

Key Features

  • SmartOnline high-performance UPS system is ideal for critical voice, data, medical and industrial network applications
  • Optional economy-mode operation with 97% efficiency for reduced power consumption and cooler operation
  • Economy mode is schedulable via PowerAlert UPS management software for daily or weekly hours of operation to enable precision output during peak operating hours and high efficiency, low BTU emission operation during off-peak times
  • Maintains continuous operation through blackouts, voltage fluctuations and surges
  • On-line, double-conversion mode provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) with zero transfer time
  • Supports operation at 50/60Hz (auto-sensing)
  • Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
  • Corrects line voltage conditions as low as 65V and as high as 150V to within 2% of selected nominal voltage
  • Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)
  • Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs
  • Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
  • Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
  • Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
  • HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP
  • UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control, remote reboot and UPS nominal voltage adjustment
  • Built-in Emergency Power Off (EPO) interface with cable
  • NEMA L5-30P input plug / NEMA 5-15R, 5-15/20R & L5-30R output receptacles
  • Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks
  • Front panel LEDs offer current monitoring and battery charge level information
  • Network grade AC, TEL/DSL or ethernet line surge suppression
  • Field replaceable, hot swappable internal batteries and external battery packs
  • $250,000 Ultimate Lifetime Insurance

Package Includes

  • SU3000XL Online, Double-Conversion UPS System
  • PowerAlert Software and cabling
  • Instruction manual with warranty information
OUTPUT  
Output Volt Amp Capacity (VA) 3000
Output kVA capacity (kVA) 3
Output Watt Capacity (watts) 2400
Output kW capacity 2.4
Output power factor 19:12
Crest Factor 3:01
Nominal Output Voltage(s) Supported 110V; 120V
Frequency compatibility 50 / 60 Hz
Frequency compatibility details Output frequency matches input nominal
on startup, defaults to 60 Hz on cold-start
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 2%
Built-in UPS output receptacles 4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
Built-in controllable switched load banks Two switchable four-outlet load banks,
(bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
Output circuit breaker 15A branch rated breaker (x2) protects 4 outlets each,
L5-30R outlet is unbreakered
Output AC waveform (AC mode) Pure Sine wave
Output AC waveform (battery mode) Pure Sine wave
INPUT  
Rated input current (at maximum load) 24A (120V)
Nominal Input Voltage(s) Supported 110V AC; 120V AC
UPS input connection type L5-30P
Input circuit breaker 40A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 30A 120V
Phase Single-Phase
BATTERY  
Full load runtime (minutes) 5 min. (2400w)
Half load runtime (minutes) 14 min. (1200w)
Expandable battery runtime Extended runtime supported via optional external battery packs
External battery pack compatibility BP72V15-2U (limit 1); BP72V28RT-3U (multi-pack compatible);
BP72V18-2US (multi-pack compatible)
DC system voltage (VDC) 72
Battery recharge rate (included batteries) Less than 6 hours from 10% to 80%
Replacement battery cartridge
(internal UPS battery replacement)
RBC96-3U
Battery Access Front panel battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION  
Voltage regulation description Online, double-conversion power conditioning
Overvoltage correction 2% output voltage regulation during overvoltages to 150
Undervoltage correction 2% output voltage regulation during undervoltages to 80
Severe undervoltage correction 2% output voltage regulation during
undervoltages to 65 (under 70% load only)
LEDS ALARMS & SWITCHES  
LED Indicators 14 LEDs indicate line power, online mode, economy/bypass
mode, on-battery, overload, battery low, replace battery and
fault status information - includes 4-LED meter display for
load and battery charge level
Alarms Audible alarm indicates UPS startup, power-failure, low-battery,
overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel switch
Switches 2 switches control off/on power status
and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION  
UPS AC suppression joule rating 570
UPS AC suppression response time Instantaneous
UPS Dataline suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC noise suppression Yes
PHYSICAL  
Installation form factors supported
with included accessories
Tower
Primary form factor Tower
UPS / Power Module dimensions
in primary form factor
(height x width x depth / inches)
10.3 x 9 x 20.5
UPS / Power Module dimensions
in primary form factor
(height x width x depth / cm)
26.2 x 22.9 x 52.1
UPS / Power Module weight (lbs) 6930%
UPS / Power Module weight (kg) 3150%
UPS Shipping dimensions
(height x width x depth / inches)
15.25 x 13 x 24
UPS Shipping dimensions
(height x width x depth / cm)
38.7 x 33 x 61
Shipping weight (lbs) 7520%
Shipping weight (kg) 34.1
Cooling method Fan
UPS housing material Steel
ENVIRONMENTAL  
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 1117
AC economy mode BTU / hr. (full load) 252.4
Battery mode BTU / hr. (full load) 121930%
AC mode efficiency rating (100% load) 88%
AC economy mode efficiency rating (100% load) 97%
Audible Noise < 45 dB at front side 1m
COMMUNICATIONS  
Communications interface USB (HID enabled); DB9 Serial; Contact closure;
EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description Supports detailed monitoring of UPS and site power conditions;
DB9 port supports RS232 and contact closure communications
PowerAlert software Included
Communications cable USB and DB9 cabling included
WatchDog compatibility Supports Watchdog application, OS and
hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER  
Transfer time No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint) 80V (100% load), 65V ( <70% load)
High voltage transfer to battery power (setpoint) 150
SPECIAL FEATURES  
Cold Start (startup in battery
mode during a power failure)
Cold-start operation supported
High availability UPS features Automatic inverter bypass; Hot swappable batteries
Green & high efficiency features High efficiency economy mode operation; Greater than 95%
efficiency - GREEN UPS; Individually controllable load banks;
Schedulable daily hours of economy mode operation
CERTIFICATIONS  
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada);
Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY  
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime Insurance

Specs Overview